MATEC Web of Conferences (Jan 2018)

SLG(Single-Line-to-Ground) Fault Location in NUGS(Neutral Un-effectively Grounded System)

  • Zhang Wenhai,
  • He Meimei,
  • Ren Jie,
  • Wen Yongke,
  • Zhang Zheng,
  • Pu Zhou,
  • Zhang Rongjian

DOI
https://doi.org/10.1051/matecconf/201816001009
Journal volume & issue
Vol. 160
p. 01009

Abstract

Read online

This paper reviews the SLG(Single-Line-to-Ground) fault location methods in NUGS(Neutral Un-effectively Grounded System), including ungrounded system, resonant grounded system and high-resistance grounded system which are widely used in Northern Europe and China. This type of fault is hard to detect and location because fault current is the sum of capacitance current of the system which is always small(about tens of amperes). The characteristics of SLG fault in NUGS and the fault location methods are introduced in the paper.