PLoS ONE (Jan 2020)
Sit bath systems: A new source of Legionella infection.
Abstract
Sit Bath Systems (SBSs) are the most common hygiene method for patients who are not self-sufficient. Therefore, the water quality of SBSs in the nosocomial environment plays a fundamental role in controlling infections for both patients and health-care workers. A long-term study on Legionella and Pseudomonas aeruginosa (P. aeruginosa) contamination was performed in SBSs (n = 20) of six Health Care Facilities (HCFs). A total of 254 water samples were analyzed following ISO procedures. The samples were positive for P. aeruginosa (46.85%) and Legionella (53.54%), respectively, both over the directive limits. Legionella isolates were identified as: Legionella pneumophila (L. pneumophila) serogroups 1, 3, and 6 and Legionella non-pneumophila species (L. anisa, L. londiniensis, L. rubrilucens, and L. nagelii). Moreover, the contamination found was studied with respect to median temperature measured (42 °C), from which two groups (A and B) could be distinguished. P. aeruginosa was found in both groups (100% of SBSs), while a higher percentage of Legionella positive samples was found in group A (75% of SBSs), compared to group B (50% of SBSs), showing how Legionella control could be carried out by using temperatures above 42 °C. An analysis of SBS water pipelines, maintenance, and disinfection treatments indicates SBSs as a new source of infection risk for both patients and health-care workers.