Frontiers in Engineering and Built Environment (Dec 2021)
Potential measures towards the reduction of cooling loads of office buildings in Ghana
Abstract
Purpose – Given the climatic context and economic challenge of Ghana in its developmental strides, energy use of office buildings continues to be a task on the economy. Therefore, the study was about finding measures that could reduce cooling loads in 10 office buildings. The paper presents the outcome of a long-term study of the thermal conditions in a selected number of office buildings in Accra and Kumasi, Ghana. Design/methodology/approach – Through long-term monitoring of environmental data, the buildings were consequently modelled in a simulation application. Thereafter, a validation of the simulation models (using regression coefficients, r2 of 0.53–0.90) was undertaken towards finding measures to reduce cooling loads. Findings – The results showed various potentials of efficient lighting, thermal mass, night ventilation, insulation to attic floors, efficient glazing, blind deployments, etc. in reducing cooling loads in the range of 2–17.5%. By combining the potential measures to study their synergistic effects on the loads, 35, 39 and 38% improvements were achieved for the low-rise, multi-storey and fully glazed office buildings. Originality/value – These potential measures ought to be incorporated in the design, specification, construction and operation of Ghanaian office buildings to reduce the burden on the economy and the environment. Now more than ever, there is the need for climatic regions to come up with empirical data that could help relieve the world's economies from the post-pandemic stress.
Keywords