Sensors (Jan 2024)

Fault Diagnosis in Wind Turbine Current Sensors: Detecting Single and Multiple Faults with the Extended Kalman Filter Bank Approach

  • Mohammed Abbas,
  • Houcine Chafouk,
  • Sid Ahmed El Mehdi Ardjoun

DOI
https://doi.org/10.3390/s24030728
Journal volume & issue
Vol. 24, no. 3
p. 728

Abstract

Read online

Currently, in modern wind farms, the doubly fed induction generator (DFIG) is commonly adopted for its ability to operate at variable wind speeds. Generally, this type of wind turbine is controlled by using two converters, one on the rotor side (RSC) and the other one on the grid side (GSC). However, the control of these two converters depends mainly on current sensors measurements. Nevertheless, in the case of sensor failure, control stability may be compromised, leading to serious malfunctions in the wind turbine system. Therefore, in this article, we will present an innovative diagnostic approach to detect, locate, and isolate the single and/or multiple real-phase current sensors in both converters. The suggested approach uses an extended Kalman filter (EKF) bank structured according to a generalized observer scheme (GOS) and relies on a nonlinear model for the RSC and a linear model for the GSC. The EKF estimates the currents in the converters, which are then compared to sensor measurements to generate residuals. These residuals are then processed in the localization, isolation, and decision blocks to precisely identify faulty sensors. The obtained results confirm the effectiveness of this approach to identify faulty sensors in the abc phases. It also demonstrates its ability to overcome the nonlinearity induced by wind fluctuations, as well as resolves the coupling issue between currents in the fault period.

Keywords