Energies (Sep 2021)

Effect of Individual Volt/var Control Strategies in <i>LINK</i>-Based Smart Grids with a High Photovoltaic Share

  • Daniel-Leon Schultis,
  • Albana Ilo

DOI
https://doi.org/10.3390/en14185641
Journal volume & issue
Vol. 14, no. 18
p. 5641

Abstract

Read online

The increasing share of distributed energy resources aggravates voltage limit compliance within the electric power system. Nowadays, various inverter-based Volt/var control strategies, such as cosφ(P) and Q(U), for low voltage feeder connected L(U) local control and on-load tap changers in distribution substations are investigated to mitigate the voltage limit violations caused by the extensive integration of rooftop photovoltaics. This study extends the L(U) control strategy to X(U) to also cover the case of a significant load increase, e.g., related to e-mobility. Control ensembles, including the reactive power autarky of customer plants, are also considered. All Volt/var control strategies are compared by conducting load flow calculations in a test distribution grid. For the first time, they are embedded into the LINK-based Volt/var chain scheme to provide a holistic view of their behavior and to facilitate systematic analysis. Their effect is assessed by calculating the voltage limit distortion and reactive power flows at different Link-Grid boundaries, the corresponding active power losses, and the distribution transformer loadings. The results show that the control ensemble X(U) local control combined with reactive power self-sufficient customer plants performs better than the cosφ(P) and Q(U) local control strategies and the on-load tap changers in distribution substations.

Keywords