International Transactions on Electrical Energy Systems (Jan 2022)
Identification Method of Dynamic Parameters of Distribution Network Lines
Abstract
Accurate network parameters are of great importance for the accurate control of the power distribution network (PDN). In fact, the line parameters of the PDN are always affected by external operating conditions. However, most of the line parameters in the PDN account are static parameters. In order to obtain the dynamic parameters that reflect the line operating condition, this study presents a method that uses only the RMS voltage of the first section of the line and the RMS voltage and power at the low-voltage side of the transformer. This study introduces the processing method of abnormal measurement data, constructs a derivative-free identification equation represented by a matrix, and uses the designed loss function combined with a heuristic method to solve the equation. An actual feeder is used in the experimental part. The experimental data show that the method has some antipower noise ability, and the identification accuracy of this method is better than that of the genetic algorithm and random search algorithm.