Study of Thermal Inertia in the Subsoil Adjacent to a Civil Engineering Laboratory for a Ground-Coupled Heat Exchanger

  • Raúl Antonio Gutiérrez-Durán,
  • Luciano. A. Cervantes,
  • Dagoberto López López,
  • Juan Peralta-Jaramillo,
  • Emerita Delgado-Plaza,
  • Guido Abril-Macias,
  • Pablo Limon-Leyva,
  • Ian Sosa-Tinoco

DOI
https://doi.org/10.3390/en16237756
Journal volume & issue
Vol. 16, no. 23
p. 7756

Abstract

Read online

This document presents a study of thermal inertia in the subsoil adjacent to the Civil Engineering laboratory of the Technological Institute of Sonora (ITSON) in the south of Sonora, Mexico, in service of the development of a solution proposal of a ground-coupled air heat exchanger for the cooling months. The research was divided into three phases: first, the monitoring of temperature in 10 layers of the ground; second, the analysis of thermal ground properties; and last, the design and simulation of a ground-coupled air heat exchanger. The objectives were to determine the variation in the thermal inertia of the soil with depth and over time and to determine the optimum depth for a ground-coupled heat exchanger system. The second objective was to develop a design proposal for a ground-coupled heat exchanger for the university laboratory. We found that the optimum depth is 3.0 m in a soil with high-compressibility clay with 21% humidity and 0.152 W/mK of thermal conductivity. However, the proposed design identified the best depth for the cooling system as 3 m considering a ground-coupled heat exchanger for a volume of 222.2 m3, corresponding to the volume of the classrooms of the building. With this design, the approach was to reduce the temperature by at least 10 °C on the hottest day (41 °C) of the year studied. We concluded that with this kind of system, the climate of the building studied could reduce the thermal load of active AC systems and reduce the energy load by 59%.

Keywords