Abstract

Read online

The paper presents a description of the method and the results of calculating the leakage reactance of high-power synchronous generator end windings using the finite element method. This reactance is one of the components of the stator leakage reactance of synchronous generators. The calculations were carried out under the assumption of a three-dimensional field distribution in a synchronous generator. The thus calculated value of the leakage reactance of the end windings was compared with the calculation results obtained using traditional, analytical formulas known from the literature. The analysis of the influence of the reactance value of the end windings on the transient waveforms at a three-phase short-circuit of the stator windings was performed based on a two-dimensional field-circuit model.