E3S Web of Conferences (Jan 2019)

Efficient Operation of Heat Source using High-temperature Chilled Water in an Advanced Office Building

  • Suzuki Yuya,
  • Imazu Misa,
  • Shinoda Jun,
  • Furukawa Ryoya,
  • Araki Yumiko,
  • Tanabe Shin-ichi,
  • Fujino Kenji,
  • Hatori Daisuke,
  • Hirasuga Nobuhiro,
  • Kato Shun,
  • Sasahara Shiori,
  • Iwata Hiroki

DOI
https://doi.org/10.1051/e3sconf/201911103071
Journal volume & issue
Vol. 111
p. 03071

Abstract

Read online

In recent years, energy conservation has become a major focus in the industrial sector. Many office buildings in Japan achieve energy savings by introducing highly efficient equipment and systems, such as high-temperature cooling water (14 °C), which increases heat source efficiency. However, such equipment requires adjustments to increase operational efficiency. In this case study, the efficiency of equipment using high-temperature cooling water was further improved through operation control optimization. The energy efficiency before and after the improvement was compared. The target building has chilled and hot water supplied to each floor from district heating and high-temperature chilled water supplied from cooling chillers on the rooftop. The energy consumption of two floors was evaluated: a subjective floor with equipment using high-temperature cooling water installed, and a common floor with a conventional system. After on-site verification, changes were made to the operation control of the cooling towers, condenser pumps, primary pumps, secondary pumps, and air handling units. As a result, the coefficient of performance of the water-cooled chiller and the whole system improved by 0.40 and 0.45, respectively. The flow rate of the air conditioning equipment using high-temperature cooling water decreased while maintaining an equivalent amount of heat extraction. In conclusion, the efficiency of the equipment was further improved by operation control optimization.