Алматы технологиялық университетінің хабаршысы (Oct 2021)

Methodology for determining of the main characteristics of a refrigeration system with condensation heat removal by radiative cooling

  • A. P. Tsoy,
  • A. S. Granovskiy,
  • R. A. Jamasheva

DOI
https://doi.org/10.48184/2304-568X-2021-3-34-41
Journal volume & issue
Vol. 0, no. 3
pp. 34 – 41

Abstract

Read online

To reduce the condensation pressure of the refrigerant in the summer, refrigeration system has been developed, in which, during periods of high air temperature, the heat of condensation is removed to the coolant, which was pre-cooled at night due to radiative cooling. A methodology has been developed for determining the main characteristics of the elements of the proposed system and calculating its daily energy consumption. The calculation shows that the proposed system with a nominal refrigerating capacity of 10 kW, using the R404a refrigerant, allows in the climate of the city of Shymkent to reduce the condensation temperature to +32.9°C, and daily energy consumption by 6.5% compared to an ordinary vapor compression refrigeration machine.

Keywords