Case Studies in Thermal Engineering (Mar 2019)

Numerical simulation study of novel air-cooled condenser with lateral air supply

  • Yu Zhou,
  • You-liang Cheng,
  • Ning Zhang,
  • Hong-bo Shi

Journal volume & issue
Vol. 13

Abstract

Read online

Uneven distribution of internal temperature and air flow field are considered to be the essential defects of the Λ-frame air-cooled condenser (ΛACC) in a power plant. Lateral air supplement to a noble, truncated cone-shaped air-cooled condenser (TCACC) is investigated by mean of numerical simulation to solve these problems fundamentally and improve the performance of the air-cooled condenser (ACC) obviously. A Circular ring, installing at the bottom of the heat transfer surface, the structure of which is optimized. According to compare a series of ACCs in different fan inlet air conditions, the TCACC with a lateral air supply (TCACCL) is obtained for heat transfer and safety. The numerical results indicate that the lateral air supplement is an effective way to improve the thermo-flow performance of TCACC. Keywords: Numerical simulation, Direct air cooled unit, Lateral air supplement, Heat transfer