Machines (Mar 2024)

An Improved Fault Localization Method for Direct Current Filters in HVDC Systems: Development and Application of the DRNCNN Model

  • Xiaohui Liu,
  • Haofeng Liu,
  • Hui Qiao,
  • Sihan Zhou,
  • Liang Qin

DOI
https://doi.org/10.3390/machines12030185
Journal volume & issue
Vol. 12, no. 3
p. 185

Abstract

Read online

This paper focus on direct current (DC) filter grounding faults to propose a novel dilated normalized residual convolutional neural network (DRNCNN) fault diagnosis model for high-voltage direct current (HVDC) transmission systems. To address the insufficiency of the traditional model’s receptive field in dealing with high-dimensional and nonlinear data, this paper incorporates dilated convolution and batch normalization (BN), significantly enhancing the CNN’s capability to capture complex spatial features. Furthermore, this paper integrates residual connections and parameter rectified linear units (PReLU) to optimize gradient propagation and mitigate the issue of gradient vanishing during training. These innovative improvements, embodied in the DRNCNN model, substantially increase the accuracy of fault detection, achieving a diagnostic accuracy rate of 99.28%.

Keywords