Abstract

Read online

Purpose. The paper supposes creation of a CFD model for calculating the air ion regime in the premises and in work areas at artificial ionization of the air by the ionizer installation indoors with considering the most important physical factors that influence the formation of ions concentration field. Methodology. The proposed CFD model for calculation of the air ion regime in work areas at artificial ionization of the air by installing ionizer indoors is based on the application of aerodynamics, electrostatics and mass transfer equations. The mass transfer equation takes into account the interaction of different polarities of ions with each other and with the dust particles. The calculation of air flow rate in the room is realized on the basis of the potential flow model by using the Laplace equation for the stream function. Poisson equation for the electric potential is used for calculation of the charged particles drift in an electric field. At the simulation to take into account: 1) influence of the working area geometric characteristics; 2) location of the ventilation holes; 3) placement of furniture and equipment; 4) ventilation regime in the room; 5) presence of obstacles on the ions dispersion process; 6) specific location of dust particles emission and ions of different polarity, and their interaction in the room and in the working zones. Findings. The developed CFD model allows determining the concentration of negative ions in the room and in the area of the human respiratory organs. The distribution of the negative ions concentration is presented in the form of concentration field isolines. Originality. The 2D CFD model for calculating the air ion regime in working areas, providing the ability to determine the ions concentration in a given place in the room was created. The proposed model is developed taking into account: placement of furniture and equipment in the room; geometric characteristics of the room; location of dust emissions sources and ions of different polarity; physical processes affecting the formation of ions concentration field. Practical value. The obtained 2D CFD model for calculating the air ions regime in working areas allow to calculate the concentration of ions at the location of the respiratory organs, taking into account the basic physical factors determining the formation of ions concentration fields. It will allow rationally arranged the ionizers in the working premises to create the comfortable working conditions for staff.

Keywords