MATEC Web of Conferences (Jan 2016)

Research on Line Patrol Strategy of 110kV Transmission Line after Lightning Strike

  • Li Mingjun,
  • Song Kunyu,
  • Ou Yuqiang,
  • Gan Tuanjie,
  • Fan Yazhou,
  • Chen Jianping

DOI
https://doi.org/10.1051/matecconf/20165505004
Journal volume & issue
Vol. 55
p. 05004

Abstract

Read online

Lightning faults occupy in the majority of instantaneous fault and reclosing can usually be successful, so power supply can be restored without immediate patrol in many cases. Firstly, this paper introduces the lightning fault positioning and identifying method. Then test electrical performance of insulators after lightning strike from 110kV lines. Data shows that lightning strike has little effect on the electric performance of insulator. Finally, illustrating disposal process of the 110 kV transmission line after lightning fault, certifying that the power supply reliability be ensured without line patrol.