Energies (Oct 2019)

Detailed Comparison of the Operational Characteristics of Energy-Conserving HVAC Systems during the Cooling Season

  • Chul-Ho Kim,
  • Seung-Eon Lee,
  • Kwang-Ho Lee,
  • Kang-Soo Kim

DOI
https://doi.org/10.3390/en12214160
Journal volume & issue
Vol. 12, no. 21
p. 4160

Abstract

Read online

To provide useful information concerning energy-conserving heating, ventilation, and air-conditioning (HVAC) systems, this study used EnergyPlus to analyze in detail their operational characteristics and energy performance. This study also aimed to understand the features of the systems under consideration by investigating the dry-bulb temperature, relative humidity, and airflow rate at major nodes in each system’s schematic. Furthermore, we analyzed the indoor environment created by each HVAC system, as well as examining the cooling energy consumptions and CO2 emissions. The HVAC systems selected for this study are the variable air volume (VAV) commonly used in office buildings (base-case model), constant air volume (CAV), under-floor air distribution (UFAD), and active chilled beam (ACB) with dedicated outdoor air system (DOAS). For the same indoor set-point temperature, the CAV’s supply airflow was the highest, and VAV and UFAD were operated by varying the airflow rate according to the change of the space thermal load. ACB with DOAS was analyzed as being able to perform air conditioning only with the supply airflow constantly fixed at a minimum outdoor air volume. The primary cooling energy was increased by about 23.3% by applying CAV, compared to VAV. When using the UFAD and ACB with DOAS, cooling energy was reduced by 11.3% and 23.1% compared with VAV, respectively.