Energies (Feb 2022)

A Numerical and Experimental Investigation of a Confluent Jets Ventilation Supply Device in a Conference Room

  • Harald Andersson,
  • Mathias Cehlin,
  • Bahram Moshfegh

DOI
https://doi.org/10.3390/en15051630
Journal volume & issue
Vol. 15, no. 5
p. 1630

Abstract

Read online

In this study, confluent jets ventilation (CJV) supply devices with three different nozzle arrays (1 × 19, 2 × 19, 3 × 19) were investigated both numerically and experimentally at two different airflow and supply air temperature set-ups. The performance of the CJV supply devices was investigated concerning thermal comfort, indoor air quality (IAQ), and heat removal effectiveness in a conference room environment. A comparison between the experimental and numerical results showed that the ϑ2¯−f model had the best agreement out of the investigated turbulence models. The numerical results showed that the size of the array had a great impact both on near-field development and on the conditions in the occupied zone. A larger array with multiple rows and a lower momentum conserved the inlet temperature and the mean age of the air better than a single-row array with a higher momentum. A larger array with multiple rows had a higher IAQ and a greater heat removal effectiveness in the occupied zone because the larger array conserved the mean age of air better and the buoyancy driven flow was slightly better at removing the heat. Because of the lower inlet velocities, they also had lower velocities at ankle level, which decreased the risk of draft and thermal discomfort.

Keywords