Determining the minor loss coefficient of cone diffusers
Abstract
This work represents results concerning different methods, used to determine the minor loss coefficient of a cone diffuser, installed at the system’s outlet. These results are compared with experimental data and numerical results, obtained after using ANSYS CFX and the data base of Pipe Flow Expert. For determining the minor loss coefficient of a cone diffuser, being installed at the system outlet and having a straight pipe section in front of it, some models in ANSYS CFX are established. These models are validated by using previously published experimental data. An empirical equation, based on the results found, enabling the accomplishment of analytical studies concerning the energy efficiency of fan systems, using an outlet diffuser, has been established.