Abstract

Read online

Distinction of weak and strong AC grids for emerging hierarchical-infeed LCC-UHVDC systems is important for planning and operation departments. However, accuracy of earlier distinction methods is limited as they were developed by empirical reasoning without rigorous theoretical analysis. Hence in this letter, hierarchical-infeed interactive effective short-circuit ratio (HIESCR) index is first used for strength evaluation of HIDC systems with complex inter-inverter interactions considered. Boundary HIESCR (BHIESCR) is also introduced in the proposed distinction method of weak and strong AC grids. That is, weak (or strong) AC grids are, respectively, identified when HIESCR is less (or greater) than BHIESCR. Second, it is shown BHIESCR remains almost unchanged as 3.0 versus various system parameters and rated operation variables based on rigorous theoretical analysis. This salient feature makes the proposed method more accurate than earlier methods. Finally, the proposed method is validated by simulations based on the PSCAD/EMTDC program.