Energies (Jun 2023)
Evaluation of the Accuracy and Frequency Response of Medium-Voltage Instrument Transformers under the Combined Influence Factors of Temperature and Vibration
Abstract
Instrument transformers are largely used to measure voltages and currents in public electricity networks. Their performance is essential for Power Quality measurements. Tests and procedures to estimate the effect of single influence factors are performed according to current standards. However, the instrument transformers are exposed simultaneously to more than one factor. The standardized procedures for their characterization with combined influence factors are under construction in Europe. The work in this paper is focused on the development of a new set-up for the determination of the accuracy and frequency response of medium-voltage transformers within the combined influence factors of temperatures and vibrations. The test set-up includes a platform for the combination of temperature and vibrations, a generating system for harmonics up to 9 kHz superposed with 35 kV, 50 Hz voltage and a reference measuring system. The results of several tests carried out on a 35 kV/100 V/50 Hz voltage transformer in the presence of these influence factors are discussed in this paper. They show that the accuracy and frequency response of the voltage transformers are more influenced by temperature than by vibrations.
Keywords