Scientific Reports (May 2024)

Control strategy for current limitation and maximum capacity utilization of grid connected PV inverter under unbalanced grid conditions

  • Jyoti Joshi,
  • Vibhu Jately,
  • Peeyush Kala,
  • Abhishek Sharma,
  • Wei Hong Lim,
  • Brian Azzopardi

DOI
https://doi.org/10.1038/s41598-024-60244-x
Journal volume & issue
Vol. 14, no. 1
pp. 1 – 16

Abstract

Read online

Abstract Under grid voltage sags, over current protection and exploiting the maximum capacity of the inverter are the two main goals of grid-connected PV inverters. To facilitate low-voltage ride-through (LVRT), it is imperative to ensure that inverter currents are sinusoidal and remain within permissible limits throughout the inverter operation. An improved LVRT control strategy for a two-stage three-phase grid-connected PV system is presented here to address these challenges. To provide over current limitation as well as to ensure maximum exploitation of the inverter capacity, a control strategy is proposed, and performance the strategy is evaluated based on the three generation scenarios on a 2-kW grid connected PV system. An active power curtailment (APC) loop is activated only in high power generation scenario to limit the current’s amplitude below the inverter’s rated current. The superior performance of the proposed strategy is established by comparison with two recent LVRT control strategies. The proposed method not only injects necessary active and reactive power but also minimizes overcurrent with increased exploitation of the inverter’s capacity under unbalanced grid voltage sag.

Keywords