Protection and Control of Modern Power Systems (Feb 2019)

Modified vector controlled DFIG wind energy system based on barrier function adaptive sliding mode control

  • Tummala S. L. V. Ayyarao

DOI
https://doi.org/10.1186/s41601-019-0119-3
Journal volume & issue
Vol. 4, no. 1
pp. 1 – 8

Abstract

Read online

Abstract Increased penetration of wind energy systems has serious concerns on power system stability. In spite of several advantages, doubly fed induction generator (DFIG) based wind energy systems are very sensitive to grid disturbances. DFIG system with conventional vector control is not robust to disturbances as it is based on PI controllers. The objective of this paper is to design a new vector control that is robust to external disturbances. To achieve this, inner current loop of the conventional vector control is replaced with sliding mode control. In order to avoid chattering effect and achieve finite time convergence, the control gains are selected based on positive semi-definite barrier function. The proposed barrier function adaptive sliding mode (BFASMC) is evaluated by testing it on a benchmark multi-machine power system model under various operating conditions. The simulated results show that the proposed method is robust to various disturbances.

Keywords