Emergency Management Science and Technology (Jan 2024)

Comparative and analysis study of pool fire radiant heat models under different view factor calculations

  • Weixin Wang,
  • Gang Tao,
  • Lijing Zhang

DOI
https://doi.org/10.48130/emst-0024-0005
Journal volume & issue
Vol. 4, no. 1
pp. 1 – 8

Abstract

Read online

According to the provisions on fire separation distance between industrial and civil buildings in the latest 'General Code for Fire Protection of Buildings and Constructions' (GB 55037-2022). Radiant heat intensity is one of the main factors in calculating the fire separation distance between buildings. Therefore, the design process involves a lot of calculation of radiant heat intensity. This paper mainly studies the prediction model of radiant heat flux. Three different view factor calculation models, Mudan, Mudan-Sparrow, and Rai-Kalelkar, are used to evaluate the influence of key factors such as the diameter of the pool and the distance between the target and the center point of the liquid pool on the calculation results of radiant heat flux. The results show that when it came to estimating the radiant heat flux, the Mudan and Mudan-Sparrow models yielded comparable results. The calculation of the Rai-Kalelkar model shows that the radiant heat flux is about half of the heat flux in the first two models. When calculating the minimum fire separation distance for combustible liquid storage tanks with a fire dike, the results show that all three models can provide a larger safety margin than the point source model.

Keywords