Energies (Jul 2023)

Field Test Method and Equivalence Analysis of Delay Characteristics of DC Electronic Current Transformer

  • Mengmeng Zhu,
  • Hongda Tang,
  • Zhaolei He,
  • Yaohua Liao,
  • Biao Tang,
  • Qunqun Zhang,
  • Hongchun Shu,
  • Yaqi Deng,
  • Fang Zeng,
  • Pulin Cao

DOI
https://doi.org/10.3390/en16155727
Journal volume & issue
Vol. 16, no. 15
p. 5727

Abstract

Read online

DC electronic current transformer is the data source of the system control and protection device, so its measurement delay has always been concerned. In this paper, the DC current transformer is modelled equivalently and the key factors affecting the delay of shunt and the remote module are analyzed. A field test method for the delay characteristics of the DC electronic current transformer is proposed. Moreover, a complex multi-state large current generator and integrated test system are developed. On the basis of the IEC 60044-8 standard transmission protocol, the accuracy of standard signal acquisition with the shunt is better than 0.2%. The maximum output current of the established testing system is 600 A. Based on the field test in an actual HVDC project, transient step and various frequency signal components are applied for analyzing.

Keywords