Buildings (Oct 2022)

Investigative Study on Adaptive Thermal Comfort in Office Buildings with Evaporative Cooling Systems (ECS) under Dry Hot Climate

  • Yuang Guo,
  • Yuxin Wang

DOI
https://doi.org/10.3390/buildings12111827
Journal volume & issue
Vol. 12, no. 11
p. 1827

Abstract

Read online

Evaporative cooling systems (ECS) in buildings, which are driven by cleaner and more sustainable energy, had been widely applied in recent years especially for the dry hot regions in summer. In this study, an investigation was conducted for office buildings by using ECS in Urumqi (China) from July to August 2021. Through subjective survey and objective measurements, 577 initial questionnaires and measured data were obtained. Outcomes showed that the indoor expectative temperature (Te) was received by 26.6 °C, 0.7 °C lower than neutral temperature (Tn). And the acceptable intervals for the 90% and 80% level were obtained at 27.1–28.9 °C and 26.4–30.3 °C, respectively. It appeared to possess a wider scope than that calculated by PMV algorithm, which further indicted that subjects have adapted to the local climate. Furthermore, the adjustment PMV models (ePMV, APMV) were found to have an effectively narrow gap comparing to the actual thermal sensation vote (TSV). The appropriate usage intervals of ePMV and APMV were quantified by Top op > 29.8 °C, 27.6 °C op < 29.8 °C, respectively. These findings may provide reference values for the revision of local energy-saving standard to some extent.

Keywords