Energies (Jun 2019)

Development of a Calibrated Simulation Method for Airborne Particles to Optimize Energy Consumption in Operating Rooms

  • Lara Febrero-Garrido,
  • José Luis López-González,
  • Pablo Eguía-Oller,
  • Enrique Granada-Álvarez

DOI
https://doi.org/10.3390/en12122433
Journal volume & issue
Vol. 12, no. 12
p. 2433

Abstract

Read online

Operating rooms are stringent controlled environments. All influential factors, in particular, airborne particles, must be within the limits established by regulations. Therefore, energy efficiency stays in the background, prioritizing safety and comfort in surgical areas. However, the potential of improvement in energy savings without compromising this safety is broad. This work presents a new procedure, based on calibrated simulations, that allows the identification of potential energy savings in an operating room, complying with current airborne particle standards. Dynamic energy and airborne particle models are developed and then simulated in TRNSYS and calibrated with GenOpt. The methodology is validated through experimental contrast with a real operating room of a hospital in Spain. A calibrated model with around 2% of error is achieved. The procedure determines the variation in particle concentration according to the flow rate of ventilation supplied and the occupancy of the operating room. In conclusion, energy savings up to 51% are possible, reducing ventilation by 50% while complying with airborne particles standards.

Keywords