Applied Sciences (Nov 2017)

Energy Performance Analysis of an Integrated Distributed Variable-Frequency Pump and Water Storage System for District Cooling Systems

  • Yichi Zhang,
  • Chuanxin Chen,
  • Jianjun Xia

DOI
https://doi.org/10.3390/app7111139
Journal volume & issue
Vol. 7, no. 11
p. 1139

Abstract

Read online

In a district cooling system (DCS), the distribution system (i.e., cooling water system or chilled water system) will continue to be a critical consideration because it substantially contributes to the total energy consumption. Thus, in this paper, a new distributed variable-frequency pump (DVFP) system with water storage (WS) for cooling water is adapted to a DCS with large end-use cooling load fluctuations. The basic principle and energy saving potential of the new system is analyzed. A case study of a DCS with a conventional central circulating pump (CCCP) system is presented to compare the energy consumption and the operating performance of CCCP and DVFP systems that are exposed to various weather conditions. The methods to perform this case study include, cooling load simulation and the modeling of two water distribution networks and systems via several commercial software packages. By replacing the throttling valves with a DVFP, the pump efficiency is increased and transportation energy consumption is reduced. Additionally, by introducing water tank storage, the cooling water is cooled at night and is released at a peak hour during the daytime, thereby further reducing the energy cost. As compared to the field test results of the CCCP system, the daily electrical energy saved by the DVFP and WS system is approximately 57% for a cooling water pump system on the hottest day in summer. This value also corresponds to approximately 10% of the energy saved for the entire system. Furthermore, additional energy could be saved under partial loading conditions.

Keywords