IET Science, Measurement & Technology (Jan 2023)

Investigation on combined effect of humidity–temperature on partial discharge through dielectric performance evaluation

  • Yatai Ji,
  • Paolo Giangrande,
  • Weiduo Zhao,
  • Vincenzo Madonna,
  • He Zhang,
  • Jing Li,
  • Michael Galea

DOI
https://doi.org/10.1049/smt2.12128
Journal volume & issue
Vol. 17, no. 1
pp. 37 – 46

Abstract

Read online

Abstract The humidity role in the partial discharge (PD) inception mechanism is quite challenging, especially when considering the environmental temperature. Indeed, there is no general rule to explain the humidity effect on the PD phenomenon. In this paper, the PD activity in inter‐turn insulation is experimentally investigated for different relative humidity (RH) conditions at three different ambient temperatures, that is, 30°C, 60°C, and 90°C. Partial discharge inception voltage (PDIV) is directly measured through a photomultiplier tube (PMT), whereas the tip‐up tests are performed aiming at monitoring both dissipation factor (tanδ) and insulation capacitance (IC). These extra measurements (diagnostic dielectric markers) allow better assessing the insulation status. The adoption of the tip‐up test enables the insulation properties measurement. Based on the tip‐up tests’ findings, the interfacial polarization process starts at 75% RH under 60°C, while the high conductivity area is already formed at 75% RH when the ambient temperature is 90°C. The water film formation deduced from the tip‐up test is then used to explain the trend of PDIV, and the validity is further proved by finite element analysis (FEA).