Journal of Engineering and Sustainable Development (May 2024)
PHASE ANGLE SHIFT AND SLOPE BASED RESTRAINT FOR INDIRECT SYMMETRICAL PHASE SHIFT TRANSFORMER PROTECTION
Abstract
This study presents a method to limit the functioning of the differential relay during the different operating conditions of an Indirect Symmetrical Phase Shift Transformer (ISPST). The proposed method depends on two thresholds; phase angle shift (PAS) between two ends of an ISPST to discriminate internal faults and inrush conditions from normal, over-excitation, and external fault conditions and slope of differential current helps to discriminate the situation of internal fault from inrush. In the first step of the algorithm, the PAS-based threshold discriminates normal, over-excitation, and external fault conditions from magnetizing inrush and internal fault conditions. In the second step, the slope-based threshold discriminates magnetizing inrush from internal fault conditions. The reliability of the proposed method has also been examined under the condition of current transformer saturation due to heavy external faults. Additionally, the comparison of the suggested and conventional methods is discussed to check the superiority of the proposed method. The proposed method eliminates the need for phase angle shift correction in the suggested method. A variety of faults in the series and excitation unit are simulated using the PSCAD/EMTDC platform to verify the approach method.
Keywords