IET Electric Power Applications (Dec 2023)

A peak time shifting phenomenon in transformer axial short‐circuit electromagnetic force due to the coupling of electromagnetic‐axial vibration

  • Yi Zhao,
  • Mingkai Jin,
  • Tao Wen,
  • Penghong Guo,
  • Weijiang Chen

DOI
https://doi.org/10.1049/elp2.12381
Journal volume & issue
Vol. 17, no. 12
pp. 1573 – 1581

Abstract

Read online

Abstract Accurately calculating axial electromagnetic force is essential to analyse transformer winding axial stability. Prior research has mainly focused on the effect of winding structure on static axial electromagnetic force and studying vibration by substituting the static force in a time‐varying function. However, the coupling effect between axial electromagnetic force and winding vibration has not been addressed, and no calculation method for the axial electromagnetic force that considers both winding meso‐structures and vibration coupling effects has been proposed. Previously the authors presented an electromagnetic force calculation model that considers winding structure characteristics, and an iterative algorithm for magnetic‐structure coupling calculation. Currently, the winding vibration model was first proposed and the dynamic calculation method was formulated. By applying the method to a typical 110kV transformer, the spatial‐temporal distribution of winding axial short‐circuit electromagnetic force was obtained. It was found that the peak value of the axial short‐circuit electromagnetic force of some windings appears at the second or third peak moment of the short‐circuit current, which is called as peak time shift phenomenon. Further stress analysis indicates that existing evaluation methods may overestimate the short‐circuit resistance of windings by only considering short‐circuit electromagnetic force under maximum peak of short‐circuit current.

Keywords