Protection and Control of Modern Power Systems (Jul 2021)

Inter-cluster voltage balancing control of a delta connected modular multilevel cascaded converter under unbalanced grid voltage

  • Oghenewvogaga J. K. Oghorada,
  • Li Zhang,
  • Huang Han,
  • Ayodele B. Esan,
  • Mingxuan Mao

DOI
https://doi.org/10.1186/s41601-021-00203-0
Journal volume & issue
Vol. 6, no. 1
pp. 1 – 11

Abstract

Read online

Abstract A new inter-cluster DC capacitor voltage balancing scheme for a delta connected modular multilevel cascaded converter (MMCC)-based static synchronous compensator (STATCOM) is presented. A detailed power flow analysis of applying negative sequence current (NSC) and zero-sequence current (ZSC) injection methods in addressing the issue of inter-cluster DC voltage imbalance under unbalance grid voltage is carried out. A control scheme is proposed which integrates both inter-cluster methods using a quantification factor Q F . This is used to achieve the sharing of the inter-cluster active power between the NSC and ZSC injection methods. An accurate method of determining the quantification factor is also presented. The proposed method offers better sub-module DC capacitor voltage balancing and prevents converter overcurrent. The influence of unbalanced grid voltage on the delta connected MMCC-based STATCOM rating using this integrated cluster balancing technique is investigated. The control scheme is verified with a 5 kV 1.2MVA MMCC-STATCOM using 3-level bridge sub-modules, and the results show the advantages of the proposed method over other inter-cluster methods.

Keywords