E3S Web of Conferences (Jan 2023)

The device for monitoring the insulation breakdown zone of power cable lines in distribution networks with isolated neutral system during high-voltage diagnostic

  • Yurov A A,
  • Storozhenko D E,
  • Lukonin A V,
  • Kuimov D N

DOI
https://doi.org/10.1051/e3sconf/202341101049
Journal volume & issue
Vol. 411
p. 01049

Abstract

Read online

The article considers an electrical device designed for diagnostic work in distribution networks of 6-10 kV, namely, the determination of damage zones in case of failure of insulating materials of cable lines during high-voltage diagnostics with a rectified voltage of negative polarity. The novelty of the developed device is its ability to connect directly to a high-voltage cable line without additional matching devices. The device is capable of detecting damage zones in lines up to 10 km remotely with an error of up to 0.2% of the cable length. The prefix allows you to fix any variants of damage to single-phase and three-phase cable lines with high transient resistance at the site of damage without the operation of “burning” insulation, which significantly reduces the time of repair work at the controlled facility.