Proceedings (Aug 2020)

The Solar-Assisted Vertical Ground Source Heat Pump System in Cold Climates—A Case Study

  • Piotr Rynkowski

DOI
https://doi.org/10.3390/proceedings2020051024
Journal volume & issue
Vol. 51, no. 1
p. 24

Abstract

Read online

In this paper, experimental studies were performed for a solar ground source heat pump system (SGSHPS) with a vertical ground heat exchanger (VGHE). The experiment was operated during the summer in 2018. The heat from the solar collector was monitored by measuring the inlet and outlet temperatures and flow rate of the heat transfer fluids. An energy equilibrium balance carried out indicates heat extraction from the solar collector to the ground heat exchanger. It has been established that clear impact is achieved within a radius of 5 m. The average temperature of the actively regenerated borehole was higher than that of the undisturbed profile, which has a direct impact on the significant benefits of the coefficient of performance (COP) of the ground source heat pump system (GSHPS) and effectively helps soil regeneration. The average efficiency ratio of the heat transferred from solar radiation to soil in the SGSHPS was 42.3%.

Keywords