Tehnika (Jan 2015)

Reliability 'H' scheme of HV/MV substations

  • Perić Dragoslav M.,
  • Tanasković Miladin R.,
  • Krnajski Vladimir Đ.,
  • Petrović Nebojša S.

DOI
https://doi.org/10.5937/tehnika1502297P
Journal volume & issue
Vol. 70, no. 2
pp. 297 – 302

Abstract

Read online

Substations (HV/MV) connect transmission and distribution systems with consumers of electric energy. The selective search method was used for calculation of substation reliability, where all arrangement elements were grouped into blocks. Subject of the analysis was H-arrangements comprising air-insulated switchgears on the high voltage side of HV/MV substations with different number of feeder and transformer bays and diverse scope of the installed switching equipment. Failure rate and duration were used as main HV/MV substation equipment reliability indices. A large number of arrangements were classified into groups, and within a group the arrangements were ranked with the use of multiple criteria. It is shown that the reliability of the electricity transit depends on the equipment of field for the transit of electricity, which favors poorly equipped field. On the other hand, the reliability of transformation of the full power depends mostly on the equipment in coupling field. It is essential that in the coupling field, there are at least two disconnectors. Installation of the switch in the coupling field is meaningful only with appropriate protection, because it further improves reliability. Conclusions are drawn for phased construction and expansion of the single pole diagram with an additional field for the transmission line.

Keywords