Energy Reports (Nov 2020)

Suitability and feasibility study on the application of groundwater source heat pump (GWSHP) system in residential buildings for different climate zones in China

  • Zhijian Liu,
  • Yulong Zhang,
  • Wei Xu,
  • Xinyan Yang,
  • Yuanwei Liu,
  • Guangya Jin

Journal volume & issue
Vol. 6
pp. 2587 – 2603

Abstract

Read online

To alleviate the pressure of energy utilization of buildings, more attention was focused on the utilization of GWSHP (groundwater source heat pump) systems. However, there have been many debates on feasibility. This paper is to study the suitability and feasibility of GWSHP systems in different climate zones. A simulation model of a GWSHP system is established based on TRNSYS software in the severe cold climate zones A and B, cold climate zones, hot summer and cold winter climate zones, and the hot summer and warm winter climate zones. Simultaneously, the reliability and energy-saving benefits of GWSHP systems in typical residential buildings situated in different climate zones are deeply analyzed. Results reveal that the operating performance of GWSHP systems is considered as the best in the climate zones that need both heating and cooling loads for residential buildings. In contrast, the energy-saving benefits of the GWSHP system in typical residential buildings are deemed to be higher in the cold climate zones and severe cold climate zones. Overall, compared with the ASHP, the economy of the system is generally better based on economic analysis.

Keywords