Inżynieria Ekologiczna (May 2016)

THE ASSESMENT OF THE EFFICENCY AND STABILITY OF WORK SEWAGE TREATMENT PLANT IN ZABAJKA

  • Dariusz Młyński,
  • Krzysztof Chmielowski,
  • Anna Młyńska

DOI
https://doi.org/10.12912/23920629/62856
Journal volume & issue
Vol. 47
pp. 123 – 130

Abstract

Read online

In the article the assessment of the efficiency and stability of work sewage treatment plant in Zabajka was performed based on the results of the physico-chemical measurements raw sewage and treated sewage noted in the period between 2010 and 2014. The analysis was performed for the following pollutants indicators: BOD5, CODCr and total suspended solids. For each of them descriptive statistics, percentage reduction the pollutants indicators and treatment plant reliability factors (WN) were calculated. The assessment of the stability of work of sewage treatment plant was performed by using control cards X for the simple test. Based on the obtained results, it was concluded that sewage treatment plant in Zabajka works properly, what is confirmed by high values of the pollutants indicators reduction and the values of WN, which are less than 1.00. The analysis of the control cards indicates instability of the treatment process only for CODCr, but it does not impact on treatment efficiency in relation to this indicator.

Keywords