Energy and Built Environment (Aug 2024)

Numerical study on critical flow velocity of ice slurry in the pipe of ice source heat pump system

  • Tao Wu,
  • Na Zhu,
  • Zhigao Hu,
  • Zhenyu Luo,
  • Pingfang Hu,
  • Fei Lei

Journal volume & issue
Vol. 5, no. 4
pp. 607 – 614

Abstract

Read online

The traditional evaporator of water source heat pump system is easy to freeze when the water source temperature is too low in winter. A novel ice source heat pump system is proposed, which can use low temperature surface water to supply heat to buildings. One of the key problems for safe transportation is velocity range of ice slurry in ice outlet pipeline. In order to study the critical flow velocity of ice slurry in the pipe, an Euler model of horizontal straight pipe and 90° elbow pipe were established by Fluent software. The influence of five factors on the critical flow velocity of two kinds of pipes, including initial ice packing fraction, ice particle size, pipe diameter, length of straight pipe and radius curvature of elbow was studied. It found that the initial ice content should be controlled from 10% to 15%. The inlet flow rate was 20% higher than the critical flow rate under the most unfavorable condition. Ice particle size was less than 0.2 mm. The total length of ice discharge pipeline was less than 50 m. Curvature radius of the bend should be met the minimum requirements of the specification of the pipe used.

Keywords