Research on the influence of outdoor wind environment on the operation characteristics of outdoor units of air conditioners in winter

  • Zhang Pengju,
  • JI Changfa,
  • Liu Zongxin,
  • Wang Zhanrong

DOI
https://doi.org/10.1051/e3sconf/202235604035
Journal volume & issue
Vol. 356
p. 04035

Abstract

Read online

Variable Refrigerant Volume multi connected air conditioning system is widely used in high-rise and super high-rise buildings because of its convenient control, flexible layout and installation and energy saving. However, for high-rise and super high-rise buildings, the outdoor wind environment has a significant impact on the installation, layout and operation performance of Variable Refrigerant Volume multi connected air conditioning system outdoor units. In this paper, the numerical simulation method is used to study the variation characteristics of inlet and exhaust temperature and speed of outdoor unit under different outdoor wind speed and wind direction in winter when the inclination angle of outdoor unit shutter of Variable Refrigerant Volume multi connected air conditioning system is 0 °, ± 30 °, ± 45 ° and ± 60 ° respectively. The results show that in winter, the air inlet and exhaust outlet should avoid the outdoor wind direction as much as possible. When there is no wind outside or the wind speed is 4m/s, the shutter angle should be maintained between 30 ° and 45 °. When the outdoor wind speed is 2m/s, the shutter angle should be maintained at about 30 °.