Energies (May 2024)
Research on Fault Identification of Hybrid Multi-Feed High-Voltage Direct Current System Based on Line Commutated Converter and Voltage Source Converter
Abstract
With the rapid development of voltage source converter (VSC) and line commutated converter (LCC) technology and the relative concentration of power and load, the inverter station of the flexible DC system is fed into the same AC bus with the conventional DC rectifier station, and the high-voltage direct current (HVDC) parallel hybrid feed system is formed in structure. As the electrical distance between the converter stations is very close, when a fault occurs in the near area, the current on the AC wiring on the VSC side will fluctuate greatly, resulting in the misoperation of the AC wiring protection. For this reason, this paper proposes a fault identification method based on VSC/LCC hybrid multi-fed HVDC system, which discriminates the fault and outputs the protection signal according to the protection criterion, and logically judges the combination of the output protection signal to identify the fault type. The simulation results show that the method can identify all kinds of faults of hybrid multi-feed DC system and solve the problem of protection misoperation of the hybrid multi-feed DC system.
Keywords