E3S Web of Conferences (Jan 2023)
Accident analysis of 220, 500 kV overhead lines of the main power systems network
Abstract
The statistical analysis of overhead lines (OHL) of the unified national power grid (UNPG) of the Central European part of the country for the previous 15 years is subjected to statistical analysis. The structure of the failure flow parameter (failure frequency) of 220 and 500 kV overhead lines with a total length of 17.6 and 8.5 thousand kilometers, respectively, is compared. It is shown that the last decade is characterized by the most favorable reliability characteristics. At the same time, a tendency was detected, when the parameter of overhead line failure flow became insignificantly dependent on the nominal voltage of the network. This fact makes us doubt the existing belief of specialists, according to which the specific (per 100 km) failure rate of overhead transmission lines decreases with the increase of the nominal voltage of the network. The above trend once again demonstrates the objective possibility of purposeful management of electric networks reliability.