Engineering Science and Technology, an International Journal (Apr 2020)

An experimental study of using water, methanol, and binary fluids in oscillating heat pipe heat exchanger

  • Anwar S. Barrak,
  • Ahmed A.M. Saleh,
  • Zainab H. Naji

Journal volume & issue
Vol. 23, no. 2
pp. 357 – 364

Abstract

Read online

The aim of this paper is studied experimentally the effect of using oscillating heat pipe heat exchanger as a heat recovery device in the air conditioning system to enhance the dehumidification capability of the cooling coil. Water and Methanol and binary fluid of Water/Methanol used as working fluids with 50% filling ratio. The dehumidification capacity of cooling coil can be enhanced by using oscillating heat pipe heat exchanger by enhancement ratio 25%, 21%, and 17% for Methanol, Binary, and Water respectively. The maximum total energy saved can be reached at 1645 W, 1849 W, and 1932 W for Water, Binary, and Methanol respectively.

Keywords