Sensors (Apr 2025)
A Partial Discharge Detection Approach in Distribution Cabinets Using a Mach–Zehnder Interferometer
Abstract
Distribution cabinets are of paramount importance in power supply systems. Internal partial discharge may result in power interruption or even the outbreak of fire. This paper proposes a partial discharge (PD) detection approach based on a fiber-optic Mach–Zehnder interferometer (MZI). The MZI method utilizes a fiber wound with a certain size and number of turns as the sensing element, which is mounted on the wall of the low-voltage distribution cabinet to monitor the partial discharge within the cabinet in real time. A true-type distribution cabinet partial discharge experimental platform is developed to validate the proposed method. Three 10 m long fiber-optic sensors with diameters of 50 mm, 80 mm, and 100 mm are designed and compared with a traditional piezoelectric transducer (PZT) for analysis. The experimental results indicate that the fiber-optic MZI sensor can effectively capture PD acoustic pulses, and the pulse amplitude is consistent with that of the PZT sensor. Moreover, compared with the PZT sensor, the fiber-optic MZI system possesses a higher frequency response and a longer effective detection time for PD pulses, demonstrating superior PD detection performance. The fiber-optic coil sensor with a diameter of 8 cm performed optimally in the experiment. The fiber-optic sensing method based on the MZI has significant potential application value in the partial discharge detection of power distribution cabinets, providing a theoretical basis for its application in engineering practice.
Keywords