E3S Web of Conferences (Jan 2020)

Failure analysis of isolation switch in transformer substation

  • Xie Yi,
  • Qiao Yaxia,
  • Zhang Hao,
  • Lou Hongjian

DOI
https://doi.org/10.1051/e3sconf/202016506023
Journal volume & issue
Vol. 165
p. 06023

Abstract

Read online

To analyze the fault cause of metal parts of isolation switch, a series of tests including macro check, penetrate testing, hardness measurement, composition tests and metallographic observation have been carried out. The experimental results showed that the failure of connecting lever was caused by improper processing, which resulted in the limitation of cracking and stress corrosion cracking. Based on this, the corresponding noteworthy key points were put forward to avoid similar accidents.