Energies (Jan 2020)

Improved Faulted Phase Selection Algorithm for Distance Protection under High Penetration of Renewable Energies

  • Eduardo Martínez Carrasco,
  • María Paz Comech Moreno,
  • María Teresa Villén Martínez,
  • Samuel Borroy Vicente

DOI
https://doi.org/10.3390/en13030558
Journal volume & issue
Vol. 13, no. 3
p. 558

Abstract

Read online

The high penetration of renewable energies will affect the performance of present protection algorithms due to fault current injection from generators based on power electronics. This paper explains the process followed for analyzing this effect on distance protection and the development of a new algorithm that improves its performance in such a scenario. First of all, four commercial protection relays were tested before fault current contribution from photovoltaic system and full converter wind turbines using the hardware in the loop technique. The analysis of results obtained, jointly with a theoretical analysis based on commonly used protection strategy of superimposed quantities, lead to a conclusion about the cause of observed wrong behaviors of present protection algorithms under a high penetration of renewables. According to these conclusions, a new algorithm has been developed to improve the detection of faulted phase selection and directionality on distance protection under a short circuit current fed by renewable energy sources.

Keywords