Energies (Oct 2024)

Research on Regulation Method of Variable-Air-Volume Air Conditioning System with “Personal Space”

  • Tingting Chen,
  • Mingyuan Zhang,
  • Shaoqing Han,
  • Yuhang Han

DOI
https://doi.org/10.3390/en17205041
Journal volume & issue
Vol. 17, no. 20
p. 5041

Abstract

Read online

In large public facilities, such as airport terminals or open-plan office spaces, the HVAC system typically consumes substantial amounts of energy. However, individuals often gather at specific areas while other zones are occupied by transient or occasional users. To minimize operational energy usage, this paper aims to reduce thermal comfort demands in non-targeted areas. This paper introduces a method for regulating the thermal environment around occupants exclusively in the variable-air-volume (VAV) air conditioning running mode. The investigation utilizes Airpak modeling and experimental verification techniques. Additionally, an analysis of temperature field and velocity field distributions within the room under the “personal space” operation mode is presented. The results suggest that adjusting the numbers of air vents, openings, airflow velocities, and air supply orientations can establish a comfortable thermal environment for inhabitants and reduce the overall ADPI value. The combined air supply mode leads to a 16.7% reduction in power usage compared to traditional full-space operation.

Keywords