Lightning Performance Evaluation of Italian 150 kV Sub-Transmission Lines

  • Fabio Massimo Gatta,
  • Alberto Geri,
  • Stefano Lauria,
  • Marco Maccioni,
  • Francesco Palone

DOI
https://doi.org/10.3390/en13092142
Journal volume & issue
Vol. 13, no. 9
p. 2142

Abstract

Read online

A significant majority of overhead transmission lines’ (OHLs) outages is due to backflashovers caused by direct lightning strikes: the realistic assessment of the lightning performance is thus an important task. The paper presents the analysis of the lightning performance of an existing 150 kV Italian OHL, namely, its backflashover rate (BFOR), carried out by means of an ATP-EMTP-based Monte Carlo procedure. Among other features, the procedure makes use of a simplified pi-circuit for line towers’ grounding system, allowing a very accurate reproduction of transient behaviours at a very low computational cost. Tower grounding design modifications, aimed at improving the OHL lightning performance, are also proposed and discussed.