E3S Web of Conferences (Jan 2021)

Simulation of energy impact of an energy recovery ventilator in Northern housing

  • Li Jing,
  • Zmeureanu Radu,
  • Ge Hua

DOI
https://doi.org/10.1051/e3sconf/202124610005
Journal volume & issue
Vol. 246
p. 10005

Abstract

Read online

The single core Energy Recovery Ventilator (ERV) used in this study is equipped with defrost control that recirculates the exhaust indoor air, while keeps the outdoor air intake damper closed. This defrost strategy has the disadvantage of reducing the outdoor air supplied to the house, which may affect the indoor air quality. First, this paper presents new correlation-based models of supply air temperature T2 after the energy recovery core during normal and defrost operation modes based on laboratory experimental data. A pre-heating coil heats the supply air from T2 to indoor air temperature. Second, a house in Montreal (4356 HDD) is simulated as a reference using TRNSYS program. Since the program cannot simulate the operation under defrost mode, the new models are connected in TRNSYS using equation boxes. The energy use of houses at three locations in northern Canada with HDD of 8798 (Inuvik), 8888 (Kuujjuaq) and 12208 (Resolute), are also simulated, without and with ERV unit. The seasonal energy used for heating the house and pre-heating the supply air is compared with results from Montreal. Compared to the case without heat recovery, the ERV unit leads to energy savings: 24% (Montreal), 26% (Inuvik), 27% (Kuujjuaq), and 27% (Resolute). Compared to the minimum standard requirements, the outdoor airflow rate due to defrost is reduced by 4.7% (223 hours) in Montreal, 19% (1043 hours) in Inuvik, 13% (701 hours) in Kuujjuaq, and 24% (1379 hours) in Resolute.