The Short-Circuit Protections in Hybrid Systems with Low-Power Synchronous Generators

  • Bartosz Rozegnał,
  • Paweł Albrechtowicz,
  • Dominik Mamcarz,
  • Natalia Radwan-Pragłowska,
  • Artur Cebula

DOI
https://doi.org/10.3390/en14010160
Journal volume & issue
Vol. 14, no. 1
p. 160

Abstract

Read online

Single-phase short-circuits are most often faults in electrical systems. The analysis of this damage type is taken for backup power supply systems, from small power synchronous generators. For these hybrid installations, there is a need for standard protection devices, such as fuses or miniature circuit breaker (MCB) analysis. Experimental research mentioned that a typical protective apparatus in low-voltage installations, working correctly during supplying from the grid, does not guarantee fast off-switching, while short-circuits occur during supplication from the backup generator set. The analysis of single-phase short-circuits is executed both for current waveform character (including sub-transient and transient states) and the carried energy, to show the problems with the fuses and MCB usage, to protect circuits in installations fed in a hybrid way (from the grid and synchronous generator set).