An Online Non-Invasive Condition Assessment Method of Outdoor High-Voltage SF6 Circuit Breaker

  • Clailton Leopoldo Da Silva,
  • Osmar Reis,
  • Frederico de Oliveira Assuncao,
  • Julio Cezar Oliveira Castioni,
  • Rafael Martins,
  • Carlos Eduardo Xavier,
  • Isac Antonio dos-Santos Areias,
  • Germano Lambert-Torres,
  • Erik Leandro Bonaldi,
  • Luiz Eduardo Borges-da-Silva,
  • Levy Ely Lacerda Oliveira

DOI
https://doi.org/10.3390/machines11030323
Journal volume & issue
Vol. 11, no. 3
p. 323

Abstract

Read online

Online monitoring of outdoor high voltage SF6 circuit breakers (HVCBs) is essential to detecting potential damages. To this end, the study of accurate and non-invasive monitoring methods has been significantly investigated in recent decades. Considering that HVCB vibration patterns carry important information about mechanical and electrical integrity and that vibration analysis requires a low level of invasiveness, this article presents methods of obtaining mechanism and reaction times using interference signals of outdoor high voltage SF6 circuit breakers (HVCBs). Compared to traditional methods of monitoring outdoor SF6 circuit breakers that are based on encoders, the proposed method presented ease of installation, as it only requires the insertion of accelerometers. The method of obtaining the mechanism time is based on the use of interference and auxiliary contact signals, in the time domain, where the accelerometer is installed, in the structure of the HVCB, makes it possible to guarantee the moment of the trip command. To obtain the reaction time of each HVCB pole, the envelope technique was applied with the Hilbert transform module of the hearing signal, filtered in a certain resonance band. The proof of the technique of analyzing the vibration of the signal in time was developed with laboratory tests of an HVCB, instrumented with accelerometers and angular encoders. The results obtained via vibration analysis were compared with those obtained via angular encoders and it was concluded that with the acceleration signals, in time, it is possible to obtain performance parameters of an HVCB from its displacement curve. Finally, the online monitoring of the circuit breaker applied in the field is presented, where the acquisition of trip current signals, the condition of the SF6 gas and extinguishing current signals were added to the instrumentation.

Keywords