Jurnal Energi Dan Manufaktur (Feb 2013)

Studi Eksperimental Pengaruh Bilangan Reynolds pada Keefektifan dan Koefisien Tekanan Penukar Panas Berkas Pipa Eliptik Susunan Berseling

  • Budi Utomo Kukuh Widodo,
  • Samsul Kamal,
  • Suhanan .,
  • I Made Suardjaja

Journal volume & issue
Vol. 5, no. 1

Abstract

Read online

Experimental studies have been conducted on the elliptic tube bundle with a diameter equivalent to 0.75 inches and the aspect ratio (AR) = 2.Tube bundle arranged alternate with 4-3-4 configuration and pitch lateral (SL) = 1.5 X axis major axis. Meanwhile pitch transverse (ST) varied 1.5 and 2 X minor axis. The Testing was carried out in a subsonic wind tunnel with wind speeds of 1 m / s - 12.6 m / s resulting Reynolds number Reb = 346-6904 and operating temperature 49 oC, 59 oC and 69 oC. Seven tubes inserted an electric heater produces uniform heat flux 3718 W/m2 - 3751 W/m2. The results show that the effectiveness of the heat exchanger (Q / P) varied from 3799 to 15, decreases exponentially at low Reynolds number and tends to asymptotic at Reynolds number above 1000. Meanwhile, the value pressure coefficient (?p/0.5?V2) with value 3.4-10 decreased continuously at low Reynolds numbers and asymptotic at high Reynolds number. In general, a bundle with a smaller ST has greater effectiveness and the pressure coefficient ranges is wider. Changes in operating temperature conseqwenly no effect on the effectiveness and the pressure coefficient at high Reynolds number.