Abstract

Read online

Traditional air conditioning systems use a significant amount of energy on dehumidification by condensing water vapor out from the air. Membrane-based air conditioning systems help overcome this problem by avoiding condensation and treating the sensible and latent loads separately, using membranes that allow water vapor transport, but not air (nitrogen and oxygen). In this work, a computational fluid dynamics (CFD) model has been developed to predict the heat and mass transfer and concentration polarization performance of a novel active membrane-based energy exchanger (AMX). The novel design is the first of its kind to integrate both vapor removal via membranes and air cooling into one device. The heat transfer results from the CFD simulations are compared with common empirical correlations for similar geometries. The performance of the AMX is studied over a broad range of operating conditions using the compared CFD model. The results show that strong tradeoffs result in optimal values for the channel length (0.6–0.8 m) and the ratio of coil diameter to channel height (~0.5). Water vapor transport is best if the flow is just past the turbulence transition around 3000–5000 Reynolds number. These trends hold over a range of conditions and dimensions.